 .jpg)
Cold Water Supply,
Drain, Waste & Vant
Rigid PVC Pipes Dimensions Based on ASTM D1785 and D2665
Table 1.13
Nominal Size (Inch)
|
Outside Diameter (mm)
|
Schedule 40
|
Schedule 80
|
Minimum
Wall Thickness
|
Nominal
Weight
|
Working
Pressure
|
Minimum
Wall Thickness
|
Nominal
Weight
|
Working
Pressure
|
Inch
|
mm
|
Kg / m
|
psi
|
Inch
|
mm
|
Kg / m
|
psi
|
½
|
21.34
|
0.109
|
2.77
|
0.248
|
600
|
0.147
|
3.73
|
0.309
|
850
|
¾
|
26.67
|
0.113
|
2.87
|
0.329
|
480
|
0.154
|
3.91
|
0.418
|
690
|
1
|
33.40
|
0.133
|
3.38
|
0.483
|
450
|
0.179
|
4.55
|
0.614
|
630
|
1¼
|
42.16
|
0.140
|
3.56
|
0.652
|
370
|
0.191
|
4.85
|
0.850
|
520
|
1½
|
48.26
|
0.145
|
3.68
|
0.779
|
330
|
0.200
|
5.08
|
1.03
|
470
|
2
|
60.32
|
0.154
|
3.91
|
1.04
|
280
|
0.218
|
5.54
|
1.43
|
400
|
2½
|
73.02
|
0.203
|
5.16
|
1.65
|
300
|
0.276
|
7.01
|
2.18
|
420
|
3
|
88.90
|
0.216
|
5.49
|
2.16
|
260
|
0.300
|
7.62
|
2.91
|
370
|
4
|
114.30
|
0.237
|
6.02
|
3.07
|
220
|
0.337
|
8.56
|
4.26
|
320
|
6
|
168.28
|
0.280
|
7.11
|
5.41
|
180
|
0.432
|
10.97
|
8.13
td> |
280
|
8
|
219.08
|
0.322
|
8.18
|
8.15
|
160
|
0.500
|
12.7
|
12.4
|
250
|
10
|
273.05
|
0.365
|
9.27
|
11.5
|
140
|
0.593
|
15.06
|
18.3
|
230
|
NOTE:
|
1.
|
Working pressure indicated in psi is maximum value and is based on water temperature of 23º C. For use at higher temperatures please refer to Table.15. |
|
2
|
Threading of only Schedule 80 pipe is recommended. For threaded pipe working pressure consult our Technical Sales Department
Schedule 80 Pipes is supplied in Gray Color. |
|
3
|
ASTM D2665 specifies PVC plastic Drain, Waste and Vent (DWV) pipes.
Schedule 40 and DWV Pipe is supplied in White Color. |
|